Littelfuse产品并非为以下用途而设计,也不应被用于这些用途:包括但不限于汽车、航空航天、医疗、救生、维生、核设施、高可靠性应用、用于手术植入体内的装置,或者在产品故障或运行无法达到理想状态的情况下会造成人身伤害、死亡或财产损失的任何其他应用。除非在适用的Littelfuse产品文档中已有明确说明。 如果将产品用于相关Littelfuse文件中未明确说明的任何其他用途,则产品不享受Littelfuse质保。 如果将产品用于相关Littelfuse文件中未明确说明的其他用途,则Littelfuse不会为因此造成的任何索赔或损失承担责任。 除非经Littelfuse另行许可,否则Littelfuse产品的销售和使用应遵守Littelfuse销售条款与条件。 "Littelfuse"包括Littelfuse, Inc.及其所有附属实体。

The Littelfuse models 111P (115 volt, ⅓ to 1hp); 233P-1.5 (230 volt, ⅓ to 1.5hp); and 233P (230 volt, ⅓ to 3hp) are single-phase pump monitors used in a variety of applications to protect from dry-well, dead-head, jammed impeller, rapid-cycling, overvoltage, and undervoltage conditions.

工作原理
A calibration adjustment allows the unit to be calibrated to your specific pumping applications, which reduces the possibility of false or nuisance tripping. A unique microcontroller-based voltage and current-sensing circuit constantly monitor the incoming power for fluctuations, overcurrent, and undercurrent conditions. When an abnormality, such as loss of suction, is detected, the product deactivates its output relay and directly disconnects the pump motor. The relay then begins its user-selectable restart delay (dry-well recovery) timer. When the timer counts to zero or power is removed and reapplied, the relay reactivates its output relay and turns the pump back on. The infrared LED communicates with a hand-held diagnostics tool called the Informer* (sold separately). The Informer displays parameters including calibration points, trip points, run time and last faults.

There are special considerations for pump cables larger than #10 AWG: In some cases where larger motors are installed with deep-set pumps, pump cables are used that exceed the relay's terminal size. In these conditions, a short splice of #10 AWG or #12 AWG may be a solution at the control box. 注: All local, state, and national electric codes should be followed when applying this solution.

: The description and operations apply to Littelfuse models 111P (115 V, ⅓ to 1 hp); 233P-1.5 (230 V, ⅓ to 1.5 hp); and 233P (230 V, ⅓ to 3 hp). These models have a sensitivity adjustment for the dry-well trip point. After calibration is complete, you can adjust the sensitivity for the dry-well/dead-head trip point from 70-90 % of the full load. This makes the unit even more adaptable to varying pumping applications. If you have a very low producing well, you increase the sensitivity closer to the 90 % mark, or if you have a very heavy producing well, you should decrease the sensitivity around the 70 % mark.

*Informer: A hand-held diagnostic tool that uses an infrared receiver to access information that can be helpful for troubleshooting the system.

功能与特色

  • Proprietary microcontroller-based circuitry
  • Onboard calibration process
  • Onboard sensitivity adjustment

请在下方查看规格、认证和存货情况并订购零部件

Catalog #Input
Voltage (V)
Input Load Range (hp)Output
Form
Termination TypeMounting MethodDimensionsWeight (lbs/g)Overcurrent Trip ClassInput AC Line Frequency (Hz)Maximum Input PowerOutput Load Rating (VA)Overvoltage Trip Voltage (%)Rapid Cycle Timer (s)Restart Delay RangeTrip Delay RangeStockSamplesCompare
产品号输入
电压(V)
输入负载范围(hp)输出
型式
端接类型安装方法尺寸规格重量(磅/克)Overcurrent Trip ClassInput AC Line Frequency (Hz)Maximum Input PowerOutput Load Rating (VA)Overvoltage Trip Voltage (%)Rapid Cycle Timer (s)Restart Delay RangeTrip Delay Range库存样品比较
111P 115 Vac1/3 - 1SPST扭矩: 13 in-lbs;导线: Solid or stranded 10 - 22 AWG#8 screws2.93 H x 5.25 W x 2.91 D in. (73.7 x 133.4 x 74 mm)0公斤125% of calibration point50 / 60 (50 will increase all delay timers by 20%)51 hp @ 120 Vac (16 A max.)132.5 Vac4 restarts allowed in 60 s periodOver/Under Voltage: 2 s; All other faults: Manual; 2 - 225 m过载电流: 5 s; Dry-well: 4 s查看 Order
111P-ENCL 115 Vac1/3 - 1SPST扭矩: 13 in-lbs;导线: Solid or stranded 10 - 22 AWG#8 screws8.3 H x 5.36 W x 3.68 D in. (210.8 x 136.1 x 93.5 mm)0公斤125% of calibration point50 / 60 (50 will increase all delay timers by 20%)51 hp @ 120 Vac (16 A max.)132.5 Vac4 restarts allowed in 60 s periodOver/Under Voltage: 2 s; All other faults: Manual; 2 - 225 m过载电流: 5 s; Dry-well: 4 s查看 Order