background-waves

系列: 235P

Littelfuse 235P Pump Monitors Provide Exceptional System Protection
产品状态| 有源i
info

The Littelfuse 235P is designed to protect 5-15 hp, 230 V, single-phase pumps from dry-well, dead-head, jammed impellers, rapid-cycle, and overvoltage and undervoltage conditions. A calibration adjustment allows the 235P to be calibrated to your specific pumping applications, reducing the possibility of false or nuisance tripping. A unique microcontroller-based voltage and current-sensing circuit constantly monitors the incoming power for fluctuations causing overcurrent and undercurrent. When an abnormality such as loss of suction is detected, the 235P deactivates its output relay and directly disconnects the pump motor. The 235P communicates with a hand-held diagnostics tool called the Informer (sold separately). The Informer displays parameters including calibration points, trip points, run time, and last faults. An external current transformer is required for operation (sold separately).

Special considerations for pump cables larger than #10 AWG: In some cases where larger motors are installed with deep-set pumps, pump cables are used that exceed the relay's terminal size. 在这些条件下,#10 AWG或#12 AWG的短接头可能是控制箱的解决方案。 Note: All local, state, and national electric codes should be followed when applying this solution.

NOTE: The 235P model has a sensitivity adjustment for the dry-well trip point. After calibration is done, you can adjust the sensitivity for the dry-well/dead-head trip point from 70-90 % of the full load.这使得该装置更能适应不同的泵送应用。 If you have a very low producing well, increase the sensitivity closer to the 90 % mark, or if you have a very heavy producing well, decrease the sensitivity around the 70 % mark.

  • 基于微控制器的专有电路
  • Onboard sensitivity adjustment
  • Adjustable restart delay
  • Built-in IR communications link
  • LED指示
  • Constant monitoring of voltage and current for reliable pump protection
  • User-adjustable sensitivity knob makes the unit more adaptable to varying pumping applications
  • Allows user to select well recovery time delay after a dry-well condition occurs, or to select manual reset
  • When used with the Informer, allows user to see stored faults, run time, and troubleshoot the pump while it’s running
  • Provides status and diagnostics for troubleshooting

235P Parts

Filters筛选

235P 应用

亮点部分

  • Used for single-phase pump protection needs
  • Null