系列: SB5000

SB5000 Industrial Shock Block® GFCI / SPGFCI / EGFPD
产品状态| 有源i
info
特殊用途接地故障断路器(SGFCI),C类和D类

工业Shock Block® SB5000系列是一款人员保护装置,旨在满足UL 943C针对专用GFCI的要求。本标准概述了专门为工业设施设计的GFCI类装置。C类GFCI旨在用于线间电压为480 V或以下、断路电平为20 mA的三相系统,而D类GFCI则用于600 V系统。 The SB5000 includes DFT harmonic filtering, an automatic self-test feature, and is compliant to the UL 1998 Software in Programmable Components standard.

接地故障断路器(GFCI),A类

The SB5000 is available as a 208 or 240 V Class A GFCI, allowing commercial kitchens, vehicle service centers, and other non-dwelling applications to meet NEC 210.8(B) for their three-phase loads up to 100 A.

器械接地故障保护设备(EGFPD)

The SB5000 is also available with adjustable protection settings as an EGFPD. EGFPD型号可设置为在6mA以及10至100mA之间、调幅为10mA的范围内跳闸。 This offers more flexibility since GFCI and SPGFCI devices are not permitted to have an adjustable trip level.

Ratings & Models

The SB5000 is available for three-phase voltages from 208 to 600 V with a maximum full load current up to 100 A. The power system can be either solidly or high-resistance grounded, and the load must be single-phase or three-phase as long as the load does not require a neutral. The standard enclosure is IP 69K/NEMA 4X and outdoor rated, suitable for all industrial environments including high temperature washdown used in food production applications. The 32 and 60A models are also available in a hygienic stainless steel enclosure, with a 10 degree sloped top and FDA compliant silicone gasket, designed to facilitate sanitation in food processing facilities and the like.

Grounding Monitor / Interrupter (GMI)

The SB5000 also monitors the equipment grounding connection between the Shock Block and load.这是C类和D类GFCI装置的必备功能,并且是A类GFCI和EGFPD装置的推荐功能。 If the ground-return path is broken, the SB5000 will trip and provide an alarm by changing the state of the alarm contacts. This monitoring circuit requires an extra (pilot) wire between the SB5000 and the load.在负载时,控制线与终端设备相连。 The other end of the termination device is connected to the equipment ground (typically the enclosure).

  • UL 943反时跳闸曲线
  • DFT(离散傅里叶变换)滤波算法
  • 最短跳闸时间<20 ms
  • 固定6 mA(UL 943)或20 mA(UL 943C)跳闸电平
  • 可选断路电平6-100mA
  • 带齐纳终端的两级接地监视器,符合UL 943C、CSA M421
  • 灵活配置
  • 保形涂料
  • 辅助触点
  • 自动自检测
  • Inverse time detection circuit protects people while also reducing the probability of nuisance tripping
  • Eliminates nuisance trips due to harmonics
  • Reduces the risk of ventricular fibrillation for leakage current of 250 mA and above
  • UL Listed GFCI and Special-Purpose GFCI personnel protection for industrial and commercial loads up to 100 A (GFCI versions)
  • Settings below 20 mA provide extra safety. The settings above 20 mA can reduce nuisance tripping on systems with high-leakage current (EGFPD versions)
  • Proactively protects from shock by tripping if continuity of ground wire between Industrial Shock Block and load is broken
  • Selectable manual reset or auto-reset for brownout, power-up, and ground monitor interruptions to fit plant safety protocols
  • Internal PWB is conformally coated to protect against corrosion and moisture
  • Alerts your SCADA system if the Shock Block is energized or tripped
  • The Shock Block will continuously test itself and will trip if there is an internal failure

SB5000 Parts

Filters筛选

SB5000 应用

亮点部分

  • For applications where people, electrical equipment, and water are present
  • Wastewater facilities
  • 餐饮
  • 商用厨房
  • 游乐园

系列: SB5000资源

GFCIs for Commercial and Industrial
播放速率
1.00x
当前时间 0:00
/
持续时间 0:00
进度:NaN%

GFCIs for Commercial and Industrial

SB5000 支持

常见问答

什么是UL 943C?它与UL 943有什么区别?

UL Standard 943 applies to Class A, single- and three-phase, Ground-Fault Circuit Interrupters (GFCI) intended for protection of personnel, for use only in grounded neutral systems in accordance with the National Electrical Code (NEC®), ANSI/NFPA 70, and the Canadian Electrical Code, C22.1 (CEC), These devices are intended for use on alternating current (AC) circuits

UL GFCI类别有哪些?

A类 - 在接地故障电流为6 mA或更高(但不是4 mA或更低)时将负载电路中断的GFCI,用于线对线电压为240 V或以下的电路。B类 - 当接地故障电流超过20 mA时将负载电路中断的GFCI。 Only used with

What does the Shock Block do?

The Shock Block detects leakage current and interrupts the circuit significantly reducing or eliminating the shock potential. One key part of the additional safety features mentioned earlier, is that the Shock Block also monitors the ground wire from the unit to the load for continuity. If the wire is broken or becomes loose, the Shock Block will signal an alarm and