ARP61S - ARP Series

系列: ARP
有问题? Contact Littelfuse Support
External overview image
滚动放大
免责声明

Littelfuse产品并非为以下用途而设计,也不应被用于这些用途:包括但不限于汽车、航空航天、医疗、救生、维生、核设施、高可靠性应用、用于手术植入体内的装置,或者在产品故障或运行无法达到理想状态的情况下会造成人身伤害、死亡或财产损失的任何其他应用。除非在适用的Littelfuse产品文档中已有明确说明。 如果将产品用于相关Littelfuse文件中未明确说明的任何其他用途,则产品不享受Littelfuse质保。 如果将产品用于相关Littelfuse文件中未明确说明的其他用途,则Littelfuse不会为因此造成的任何索赔或损失承担责任。 除非经Littelfuse另行许可,否则Littelfuse产品的销售和使用应遵守Littelfuse销售条款与条件。 "Littelfuse"包括Littelfuse, Inc.及其所有附属实体。

The ARP Series is used in systems where equal run time for two motors is desirable. The selector switch allows selection of alternation of either load for continuous operation. LED's indicate the status of the output relay. This versatile series may be front panel mounted (BZ1 accessory required) or 35 mm DIN rail mounted with an accessory socket.


Operation Alternating: When the rotary switch is in the "alternate" position, alternating operation of Load A and Load B occurs upon the opening of the control switch S1. To terminate alternating operation and cause only the selected load to operate, rotate the switch to position "A" to lock Load A or position "B" to lock Load B. The LEDs indicate the status of the internal relay and which load is selected to operate.
: Input voltage must be applied at all times for proper alternation. The use of a solid-state control switch for S1 may not initiate alternation correctly. S1 voltage must be from the same supply as the unit's input voltage (see connection diagrams on datasheet). Loss of input voltage resets the unit; Load A becomes the lead load for the next operation.
Duplexing (Cross Wired): Duplexing models operate the same as alternating relays and when both the Control (S1) and Lag Load (S2) Switches are closed, Load A and Load B energize simultaneously.
The DPDT 8-pin, cross-wired option, allows extra system load capacity through simultaneous operation of both motors when needed. Relay contacts are not isolated.

参数 (将鼠标移到目标文字上面可显示详情) 数值
Input Voltage (V) 230 Vac
Input Tolerance (%) -20% - 10%
Input AC Line Frequency (Hz) 50 / 60
Maximum Output Voltage (V) 250
Output Type Electromechanical Relay
Output Form SPDT
Output Load Rating (VA) 10 A resistive @ 120/240 Vac and 28 Vdc; 1/3 hp @ 120/240 Vac
Termination Type Octal 8-pin plug-in
Mounting Method Plug-in socket
Operating Temperature -20° to 60°C (-4° to 140°F)
Storage Temperature (F/C) -30° to 85°C (-22° to 185°F)
Dimensions 3.2 H x 2.39 W x 1.78 D in. (81.3 x 60.7 x 45.2 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes
如要索取产品环境信息,请填写 产品环境信息申请表