ECSW4MACT - ECSW Series

系列: ECSW
有问题? Contact Littelfuse Support
External overview image
滚动放大
免责声明

Littelfuse产品并非为以下用途而设计,也不应被用于这些用途:包括但不限于汽车、航空航天、医疗、救生、维生、核设施、高可靠性应用、用于手术植入体内的装置,或者在产品故障或运行无法达到理想状态的情况下会造成人身伤害、死亡或财产损失的任何其他应用。除非在适用的Littelfuse产品文档中已有明确说明。 如果将产品用于相关Littelfuse文件中未明确说明的任何其他用途,则产品不享受Littelfuse质保。 如果将产品用于相关Littelfuse文件中未明确说明的其他用途,则Littelfuse不会为因此造成的任何索赔或损失承担责任。 除非经Littelfuse另行许可,否则Littelfuse产品的销售和使用应遵守Littelfuse销售条款与条件。 "Littelfuse"包括Littelfuse, Inc.及其所有附属实体。

The ECSW Series of single-phase, AC window, current sensors includes adjustable overcurrent and undercurrent trip points. Detects locked rotor, jam, loss of load, an open heater or lamp load, a broken belt, or loss of suction. LED's aid in trip point adjustment and provide fault indication. The built-in toroidal sensor eliminates the need for an external current transformer. The output can be electrically latched after a fault, or automatically reset. Remote resetting of a latched output by removing input voltage. The unit includes switch selectable zero current detection and normally de-energized or energized output operation. Time delays are included to improve operation and eliminate nuisance tripping.


See datasheet for operation detail.

参数 (将鼠标移到目标文字上面可显示详情) 数值
Input Voltage (V) 120 Vac
Input Tolerance (%) -20% - 10%
Input AC Line Frequency (Hz) 50 / 60
Output Type Electromechanical relay
Output Form Isolated SPDT
Output Load Rating (VA) 10 A resistive @ 240 Vac; 1/4 hp @ 125 Vac; 1/2 hp @ 250 Vac
Time Delay Range 0.15 - 7 s adjustable
Time Delay Tolerance (%) Guaranteed range
Response Time (ms) ≤75 ms
Trip Delay Sensing on Startup (s) Fixed: 0.1 - 6 s in 1 s increments
Trip Point Range 2 - 20 adjustable
Undercurrent Trip Point <250 mA turns typical
Sensor Type Toroid; through hole wiring for up to #4 AWG (21.1 mm²) THHN wire
Sensor Mode Over and undercurrent trip points (window current sensing)
Sensor Tolerance Guaranteed range
Current Sensor Range Steady - 50A turns; Inrush - 300A turns for 10s
Sensor Frequency (Hz) 45/500
Insulation Resistance ≥100
Surge Protection IEEE C62.41-1991 Level A
Type of Detection Peak detection
Termination Type 0.197 in. (5 mm) terminal blocks for up to #12 (3.2 mm²) AWG wire
Mounting Method Surface mount with two #6 (M3.5 x 0.6) screws
Operating Temperature -40° to 60°C (-40° to 140°F)
Storage Temperature (F/C) -40° to 85°C (-40° to 185°F)
Humidity 95% non-condensing
Dimensions 3.5 H x 2.5 W x 1.75 D in. (88.9 x 63.5 x 44.5 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes