202-RP - 202 Series – Three-Phase Voltage Monitor Relay Series

External overview image
滚动放大
免责声明

Littelfuse产品并非为以下用途而设计,也不应被用于这些用途:包括但不限于汽车、航空航天、医疗、救生、维生、核设施、高可靠性应用、用于手术植入体内的装置,或者在产品故障或运行无法达到理想状态的情况下会造成人身伤害、死亡或财产损失的任何其他应用。除非在适用的Littelfuse产品文档中已有明确说明。 如果将产品用于相关Littelfuse文件中未明确说明的任何其他用途,则产品不享受Littelfuse质保。 如果将产品用于相关Littelfuse文件中未明确说明的其他用途,则Littelfuse不会为因此造成的任何索赔或损失承担责任。 除非经Littelfuse另行许可,否则Littelfuse产品的销售和使用应遵守Littelfuse销售条款与条件。 "Littelfuse"包括Littelfuse, Inc.及其所有附属实体。

The 202 series is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-600VAC, 50/60Hz motors regardless of size. The 202-RP monitors the phase rotation of 3-phase systems and trips on reverse phase only. Critical applications include fan motors, scroll compressors, grinders, conveyor systems, elevators and escalators. Both products provide a user selectable nominal voltage setpoint and some models automatically select between the 200V and 400V range.

This unique microcontroller-based voltage and phase-sensing device constantly monitors the 3-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the 202 series's output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels. The 202 series includes advanced single LED diagnostics. Five different light patterns distinguish between faults and normal conditions. The 202-RP monitors the phase rotation of 3-phase systems and trips on reverse phase only. Critical applications include fan motors, scroll compressors, grinders, conveyor systems, elevators and escalators. The status light turns green and the relay is activated when rotation is correct.

参数 (将鼠标移到目标文字上面可显示详情) 数值
Input Voltage (V) 190 - 480 Vac
Input Tolerance (%) ±10%
Maximum Input Power 5
Input AC Line Frequency (Hz) 50 / 60 (50 will increase all delay timers by 20%)
Input Phase Sequence A; B; C
Output Form SPDT
Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac
Restart Delay Range Manual; 2 - 300 s adjustable
Repeat Accuracy (%) ±0.5%
Trip Delay Range Under/Over Voltage: 4 s; Unbalance/Phase faults: 2 s
Trip Point Accuracy (%) ±1%
Overvoltage Trip Voltage (%) 110%
Overvoltage Reset Voltage (%) 107%
Undervoltage Trip Voltage 90%
Undervoltage Reset Voltage (%) 93%
Voltage Unbalance Trip Point (%) 6%
Voltage Unbalance Reset (%) 4.50%
Dielectric Breakdown ≥1960
Termination Type 0.25 in male quick connect
Mounting Method 1/4 in socket head cap screw (customer supplied)
Operating Temperature -40° to 70°C (-40° to 158°F)
Humidity 95% non-condensing
Dimensions 2.5 H x 2.5 W x 1.4 D in. (63.5 x 63.5 x 35.6 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes
如要索取产品环境信息,请填写 产品环境信息申请表